Description
Altronix T1RAL3F8 Access and Power Integration Kit
Altronix T1RAL3F8 rack kit is pre-assembled and consists of Trove1AL1R enclosure/backplane with factory installed Altronix power supply/ charger(s) and sub-assemblies.
Key Features:
Power Supply (eFlow6NB):
Input
- Voltage: 120VAC, 60Hz, 3.5A max.
- Fusing: 5A / 250V.
Output
- Voltage: Factory set at 24VDC.
- Current: 6A continuous.
- Maximum Supply Current for Main and Aux. Outputs on eFlow6NB Power Supply board, ACMS8 Access Power Controllers and PDS8 Power Distribution Modules outputs is 5.6A.
- Auxiliary: Class 2 power-limited @ 1A (unswitched).
- Other: Overvoltage protection. Filtered and regulated.
Battery Backup
- Built-in charger for sealed lead acid or gel type batteries (if batteries are required, install separate battery enclosure RE2).
- Automatic switch over to stand-by battery when AC fails.
- Zero voltage drop when unit switches over to battery backup (AC failure condition).
Fire Alarm Disconnect
- Supervised: Latching or non latching.
- EOL: 10K Resistor.
Supervision
- AC Failure: Form C contacts.
- Battery: Form C contacts.
- Low DC Power Shutdown: Shuts down DC output terminals if battery voltage drops below 70-75% for 24V units. Prevents deep battery discharge.
Indicators LED
- Input: 120VAC is present.
- DC Output: Powered.
- Battery: Discharged or not connected.
Power Distribution Module (PDS8):
Input
- Voltage: 24VDC from eFlow6NB and 12VDC from VR6.
- Fusing: 10A / 250V.
Output
- Voltage: 12 or 24VDC individually selectable.
- Fuses Rating: 3A / 32VDC.
Indicators (LED's)
- DC Output: Eight (8) individual output LEDs.
Access Power Controller (ACMS8):
Input
- Voltage: 24VDC from eFlow6NB and 12VDC from VR6.
- Fusing: 15A / 32V.
Output
- Voltage: 12 or 24VDC individually selectable.
- Eight (8) selectable 12VDC - 24VDC independently controlled outputs or eight (8) indepently controlled Form C relay outputs:
- a) Fail-Safe and/or Fail-Secure power outputs.
- b) Form C Relays. 28VAC or VDC @ 2.5A Rated.
- c) Auxiliary power outputs (unswitched).
- d) Any combination of the above.
- Any of the eight (8) fuse protected power outputs are selectable to follow power Input 1 or Input 2.
- Individual outputs may be set to OFF position for servicing.
- Fuses Rating: 2.5A / 32VDC.
Indicators (LED)
- Red LEDs: Outputs are triggered (relays energized).
- Blue LED: FACP disconnect is triggered.
Individual voltage LEDs
- Green: 12VDC
- Red/Green: 24VDC
Physical and Environmental (T1RAL3F8):
Temperature
- Operating: 0° C to 49° C (32° F to 120° F).
- Storage: - 20° C to 70° C ( - 4° F to 158° F).
Relative Humidity
- Relative Humidity 85% +/- 5%.
BTU/Hr (approx.):
- 115 BTU/Hr.
Downloads
Datasheet
Altronix T1RAL3F8 Datasheet